Cleanroom air changes per hour: how to calculate and verify them
Updated · 3 min read
On this page
Air changes per hour (ACPH) is how many times the room's volume of clean, HEPA-filtered air is supplied every hour. It's one of the numbers a pharmacy inspector reads first on a USP <797> report, and one of the easiest to get wrong.
The formula
ACPH = total supply airflow (cfm) × 60 ÷ room volume (ft³)
- Total supply airflow is the sum of the measured airflow at every HEPA supply diffuser in the room, in cubic feet per minute.
- 60 converts minutes to hours.
- Room volume is floor area × ceiling height, in cubic feet.
In metric: ACPH = total supply (m³/h) ÷ room volume (m³).
A worked example
A buffer room is 10 ft × 20 ft with a 9 ft ceiling:
- Volume: 10 × 20 × 9 = 1,800 ft³
- Four ceiling HEPA diffusers, measured at 240, 255, 250 and 245 cfm: total 990 cfm
- ACPH: 990 × 60 ÷ 1,800 = 33 ACPH
That passes the USP <797> minimum of 30 for an ISO 7 buffer room, but not by much: a diffuser losing 50 cfm as its filter loads would take the room to about 31.
The cleanroom classification calculator does this from a list of diffuser readings and the room's size.
Measuring the supply airflow
Measure each diffuser with a capture hood (flow hood) sized to the diffuser, and record each reading on the report rather than only the total. Readings per diffuser show which filter is loading and make the next certification easier to compare.
Velocity readings across a filter face multiplied by its area can stand in where a capture hood won't fit, but they're less accurate for diffusers with grilles or perforated faces. Note the method used.
USP minimums
| Room | Minimum ACPH |
|---|---|
| ISO 7 buffer room (USP <797>) | 30 total HEPA-filtered, at least 15 of them from the HVAC through ceiling HEPA filters |
| ISO 8 ante-room (USP <797>) | 20 |
| ISO 7 hazardous-drug buffer room (USP <800>) | 30 |
| Containment segregated compounding area (USP <800>) | 12 |
The primary engineering control's HEPA-filtered air can count toward a buffer room's 30, but not toward the 15 that must come from the HVAC. Background on these rooms is in USP <797> cleanroom certification.
ISO 14644 itself doesn't set air change rates; a room is classified by its particle counts (see ISO 14644-1 classification). Higher ACPH helps a room reach and recover to its class, which is why design rates for ISO 7 and cleaner rooms usually sit well above the USP minimums.
Mistakes that make ACPH wrong
- Using design airflow instead of measured. The drawings say what the system was meant to deliver, not what it delivers now with loaded filters.
- Counting return or exhaust airflow. ACPH is HEPA-filtered supply air.
- Counting the PEC twice, or counting it toward the HVAC's 15.
- The wrong ceiling height. Use the actual ceiling of the room, not the height of the building's floor-to-floor or a soffit.
- Mixing units. Square metres times feet is a common one; keep it all in feet or all in metres.
Doing this on every job
Certorum calculates ACPH from each diffuser reading and the room's size as you enter them, checks it against the room's minimum, and keeps the per-diffuser readings on the report, so next visit you can see which filter is falling off.
Certorum does these checks as you type
Enter readings on a phone or tablet on site: each one is checked against the standard and the unit's own set points, and the certificate and invoice are ready when you sign off. Free for up to 40 units.
More guides
- ASHRAE 110 fume hood testing: procedure, ratings and acceptance criteria
- Biosafety cabinet classes and types explained
- What a biosafety cabinet certification report should include
- How often do biosafety cabinets, fume hoods and cleanrooms need certification?
- ISO 14644-1:2015 cleanroom classification: class limits, sample locations and sample volume
- Biosafety cabinet certification: NSF/ANSI 49 field tests and acceptance criteria
- USP <797> cleanroom certification: what's tested every six months
- Handbook 44 scale test procedures
- NIST Handbook 44 scale tolerances explained
- Placed-in-service reports for scales
- Test weights for scale service